Timing verification (3i0 mode), N figure 255, Table 159 – Basler Electric BE1-11t User Manual

Page 378

background image

366

9424200995 Rev H

Figure 255. BESTlogicPlus Settings (3I0 Mode)

Table 159. Pickup Test Settings (3I0 Mode)

Sensing Input Type

Range

Pickup Setting

Time Delay

5 A

Low

0.5 A

0 ms

Middle

5.0 A

0 ms

High

20.0 A

0 ms

1 A

Low

0.1 A

0 ms

Middle

1.0 A

0 ms

High

4.0 A

0 ms

Step 4: Prepare to monitor the 50-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 255).

Step 5: Connect a current source to terminals D1 and D2 (A-phase).

Step 6: Slowly increase the A-phase current until OUT2 closes and record the pickup. Verify that there

is a 50-1-Residual target on the front-panel display. Slowly decrease the applied current until
OUT2 opens and record the dropout.

Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record

the results.

Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.

Step 9: (Optional.) Repeat steps 1 through 8 for 50-2, 50-3, 50-4, 50-5, 50-6, 50-7, 50-8, and 50-9.

Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source. In step 5, replace D1 with

F1, D2 with F2, etc.

Timing Verification (3I0 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the first row of test settings in Table 160 to the BE1-11t for settings group 0.

Table 160. Timing Test Settings (3I0 Mode)

Pickup Setting

Time Delay

0.5 A

2,000 ms

0.5 A

5,000 ms

0.5 A

10,000 ms

Step 2: Prepare to monitor the 50-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect and apply 0.45 A to BE1-11t terminals D1 and D2 (A-phase).

Instantaneous Overcurrent (50) Test

BE1-11t