Een (figure 43), Table 16 – Basler Electric BE1-11t User Manual
Page 67

9424200995 Rev H
55
Figure 43. Overvoltage Settings Screen
Table 16. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled,
One of Three,
Two of Three,
or Three of Three
n/a
n/a
Disabled
Pickup
0 or 1 to 300
0.1
volts
0
Timing Mode
Definite or Inverse
n/a
n/a
Definite
Time Delay (Definite Timing)
50 to 600,000
varies
milliseconds
50
Time Dial (Inverse Timing)
0 to 9.9
0.1
units
0
BE1-11t
Phase Overvoltage (59P) Protection