Pickup verification (roc frequency) – Basler Electric BE1-11t User Manual
Page 370

358
9424200995 Rev H
Step 3: Connect and apply a 120 Vac, 60-hertz voltage source to terminals C13 (A-phase) and C16
(neutral).
Step 4: Step the frequency of the applied voltage down to 55-hertz. Measure the time delay and record
the result.
Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delays listed in Table 152. Record the
results.
Step 6: (Optional.) Repeat steps 1 through 5 for settings groups 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 81-2, 81-3, 81-4, 81-5, 81-6, 81-7, and 81-8.
Pickup Verification (ROC Frequency)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 153 to the BE1-11t. Reset all
targets.
Table 153. Operational Settings (ROC Frequency)
Setting
Value
BESTCOMSPlus
Screen
Description
Element Mode
Rate of
Change
Protection, Frequency
(81-1)
Enables 81-1 function for Rate of
Change mode
Source
Phase VT
Protection, Frequency
(81-1)
Sets source to Phase VT
Pickup
10 Hz/sec
Protection, Frequency
(81-1)
Sets pickup to 10 Hz/sec
Voltage Inhibit
40 V
Protection, Frequency
(81-1)
Sets voltage inhibit pickup to 40 V
Over Frequency
Inhibit
64 Hz
Protection, Frequency
(81-1)
Sets over frequency inhibit to 64 Hz
Under Frequency
Inhibit
46 Hz
Protection, Frequency
(81-1)
Sets under frequency inhibit to 46
Hz
81-1 ROC
Enabled
Target Configuration,
Targets
Enables ROC target for 81-1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 252.
•
Blocking is disabled.
•
OUT1 closes for 81-1 Trip.
•
OUT2 closes for 81-1 Pickup.
•
Fault recording is enabled.
Figure 252. BESTlogicPlus Settings (ROC Frequency)
Step 3: Prepare to monitor the 81-1 function operation. Operation can be verified by monitoring OUT2
Frequency (81) Test
BE1-11t