Logic connections, Operational settings – Basler Electric BE1-11t User Manual
Page 71

9424200995 Rev H
59
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.
Logic Connections
Auxiliary overvoltage element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The auxiliary overvoltage element logic block is illustrated in Figure 44. Logic inputs
and outputs are summarized in Table 18.
Figure 44. Auxiliary Overvoltage Element Logic Block
Table 18. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 59X function when true
Trip
Output
True when the 59X element is in a trip condition
Pickup
Output
True when the 59X element is in a pickup condition
Operational Settings
Auxiliary overvoltage element operational settings are configured on the Overvoltage (59X) settings
screen (Figure 45) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 19.
Figure 45. Auxiliary Overvoltage Settings Screen
BE1-11t
Auxiliary Overvoltage (59X) Protection