Timing verification (ig mode) – Basler Electric BE1-11t User Manual
Page 385

9424200995 Rev H
373
Timing Verification (IG Mode)
Time Delay Range = 0 to 60,000 ms
Timing Accuracy =
±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,942 ms
2,058 ms
P / F
5
5,000 ms
4,927 ms
5,073 ms
P / F
5
10,000 ms
9,902 ms
10,098 ms
P / F
BE1-11t
Instantaneous Overcurrent (50) Test
This manual is related to the following products: