Remote analog output metering, Remote rtds configuration, Configuration settings – Basler Electric BE1-11t User Manual

Page 530

background image

518

9424200995 Rev H

Figure 333. Module 1 Output #1 Screen

Table 214 summarizes the configuration settings for remote analog outputs.

Table 214. Configuration Settings for Remote Analog Outputs

Setting

Range

Increment

Unit of Measure

Default

Param Selection

Voltages, Currents, Frequency,

Power, etc.

n/a

n/a

VA

Output Type

Voltage or Current

n/a

n/a

Voltage

Param Min

–99,999.9 to 99,999.9

0.1

n/a

–99,999.9

Param Max

–99,999.9 to 99,999.9

0.1

n/a

–99,999.9

Min Input Current

4 to 20

0.01

milliamps

4

Max Input Current

4 to 20

0.01

milliamps

20

Min Input Voltage

0 to 10

0.01

volts

0

Max Input Voltage

0 to 10

0.01

volts

10

Remote Analog Output Metering

Analog output metering values are obtained through BESTCOMSPlus by using the Metering Explorer to
open the Analog Metering, Analog Outputs tree branch. BESTCOMSPlus must be online with the BE1-11t
to view analog output metering. Alternately, values can be obtained through the front-panel display by
navigating to Metering > Analog Metering > Analog Output.

Remote RTDs Configuration

The RTD module provides 12 RTD inputs. The BE1-11t supports two RTD modules at once. The RTDs
are always monitored and their status is displayed on the appropriate metering screens. The BE1-11t
reports Out of Range when an RTD module is disconnected.

Protection settings for remote RTDs are described in the

Resistance Temperature Detector (49RTD)

Protection

chapter.

Configuration Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Remote RTD

HMI Navigation Path: Settings Explorer, RTD Types

Configuration settings are made using the BE1-11 plugin for BESTCOMSPlus. Before making
configuration settings, remote module communications must be configured on the System Parameters,
Remote Module Communications screen. To program the configuration settings, use the Settings
Explorer to open the Programmable Outputs, Remote RTD, RTD Type Selection tree branch and select
RTD Type Selection. Use the drop-down menu to select RTD Type. Refer to Figure 334.

RTD Module

BE1-11t