beautypg.com

Programmable alarm, Element blocking, Logic connections – Basler Electric BE1-11t User Manual

Page 51: Operational settings

background image

9424200995 Rev H

39

Programmable Alarm

A 24 Volts per Hz alarm occurs during overexcitation so that corrective action can be taken before the 24
function trips. The alarm appears on the front-panel display, web page interface, and on the Alarms
metering screen in BESTCOMSPlus. Refer to the

Alarms

chapter for information about programming

alarms.

When the Alarm Pickup setting is exceeded, a timer is initiated and begins timing toward a trip. The
duration of the timer is established by the alarm Time Delay setting. An alarm Time Delay setting of zero
(0) makes the alarm instantaneous with no intentional time delay.

If the alarm pickup condition persists for the duration of the alarm Time Delay setting, the 24 Volts per Hz
alarm becomes true. If the alarm pickup condition subsides before the alarm time delay expires, the timer
is reset and no corrective action is taken.

Table 7 lists the programmable alarm settings.

Table 7. Programmable Alarm Settings

Setting

Range

Increment

Unit of Measure

Default

Alarm Pickup

0 or 0.5 to 6

0.01

V/Hz

0

Alarm Time Delay

0 or 50 to 600,000

varies

milliseconds

0

Element Blocking

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Overexcitation element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus.
The overexcitation element logic block is illustrated in Figure 33. Logic inputs and outputs are
summarized in Table 8.

Figure 33. Overexcitation Element Logic Block

Table 8. Logic Inputs and Outputs

Name

Function

Purpose

Block

Input

Disables the 24 function when true

Trip

Output

True when the 24 element is in trip condition

Pickup

Output

True when the 24 element is in pickup condition

Operational Settings

Overexcitation operational settings are configured on the Overexcitation (24) settings screen (Figure 34)
in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 9.

BE1-11t

Overexcitation (24) Protection