27x - auxiliary undervoltage protection, 46 - negative-sequence current protection, 47 - negative-sequence voltage protection – Basler Electric BE1-11t User Manual

Page 473

background image

9424200995 Rev H

461

Inhibit Level
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Inhibit Ratio ..................................................... 102%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±8% or ±4 cycles, whichever is greater
Refer to the

Time Curve Characteristics

chapter for

information on available timing curves.

27X - Auxiliary Undervoltage Protection

Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio .................................................... 102%

±1%

Inhibit Level
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Inhibit Ratio ..................................................... 102%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±4 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±8% or ±4 cycles, whichever is greater
Refer to the

Time Curve Characteristics

chapter for

information on available timing curves.

46 - Negative-Sequence Current Protection

Negative-sequence current protection is available when a 50 or 51 element is configured in I2 mode.
Refer to Instantaneous Overcurrent or Inverse Overcurrent for operational specifications.

47 - Negative-Sequence Voltage Protection

Negative-sequence voltage protection is available when a 27X or 59X element is configured in V2 mode.
Refer to Auxiliary Overvoltage or Auxiliary Undervoltage for operational specifications.

49RTD - Resistance Temperature Device Protection (Optional)

Pickup

Setting Range ........................................................... 0 to 250

°

C (32 to 482

°

F)

Accuracy....................................................................

±2% or ±2

°

C (

±3.6

°

F), whichever is greater

Reset/Pickup Ratio .................................................... 105% / 95%

±1% (over / under) or 5

°

C minimum

BE1-11t

Specifications - 25 Hz Operation