Lockout functions (86), Element operation, Logic connections – Basler Electric BE1-11t User Manual

Page 133: Operational settings

background image

9424200995 Rev H

121

Lockout Functions (86)

Two lockout function (86) elements can be used to prevent operation of circuit breakers or other devices
until the condition causing lockout is eliminated.

The two, identical lockout function elements are designated 86-1 and 86-2. Element logic connections are
made on the BESTlogic

Plus screen in BESTCOMSPlus® and element operational settings are

configured on the Lockout Functions screen in BESTCOMSPlus. A summary of the logic inputs and
outputs and operational settings appears at the end of this chapter.

BESTCOMSPlus Navigation Path: Settings Explorer, Control, Lockout Functions (86)

HMI Navigation Path: Settings Explorer, Control, Lockout 86

Element Operation

When the Set input is asserted, the output of the function becomes true (breaker opens). When the Reset
input is asserted, the output becomes false (breaker closes). If both inputs are asserted at the same time,
the Set input will have priority and drive the output to true. The state of the function is stored in nonvolatile
memory.

Logic Connections

Lockout function element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus.
The lockout function element logic block is illustrated in Figure 83. Logic inputs and outputs are
summarized in Table 46.

Figure 83. Lockout Function Element Logic Block

Table 46. Logic Inputs and Outputs

Name

Logic Function

Purpose

Set

Input

Sets the state of the output to true

Reset

Input

Sets the state of the output to false

Output

Output

True when the Set input is asserted

Operational Settings

Lockout function element operational settings are configured on the Lockout Functions (86) settings
screen (Figure 84) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 47.

Figure 84. Lockout Functions Settings Screen

BE1-11t

Lockout Functions (86)