Mounting
RTD modules are contained in a potted plastic case and may be mounted in any convenient position
using UNC ¼-20 or equivalent screws. Hardware selection should be based on any expected
shipping/transportation and operating conditions. The torque applied to the mounting hardware should not
exceed 65 in-lb (7.34 N•m).
See Figure 312 for RTD module overall dimensions. All dimensions are shown in inches with millimeters
in parenthesis.
Figure 312. RTD Module Overall Dimensions
Connections
RTD module connections are dependent on the application. Incorrect wiring may result in damage to the
module.
Note
Be sure that the RTD module is hard-wired to earth ground with no
smaller than 12 AWG (3.31 mm
2
) copper wire attached to the chassis
ground terminal on the module.