Table 96 – Basler Electric BE1-11t User Manual

Page 303

background image

9424200995 Rev H

291

Table 95. CT Input Circuit Settings for Non-transformer or Wye-only Application

Transformer

Connection

CT Input

Connection

BE1-11t Settings

Compensation Applied

TX

CT

Phase

Rotation

N/A

WYE

NA

WYE

WYE

NONE

DAB

NA

DAB

WYE

NONE

DAC

NA

DAC

WYE

NONE

All WYE

All WYE

WYE

WYE

DAB

NONE

∗ Special case where all transformer windings and all CTs are connected in wye.

Table 96. CT Input Circuit Settings 1 for Delta/Wye Circuit Applications

Transformer

Connection

CT Input

Connection

BE1-11t Settings

Compensation Applied

TX

CT

Phase

Rotation

WYE


WYE


WYE


WYE

DAB for DAB

connections

DAC for DAC

connections

NONE

WYE


DAB

WYE

DAB

WYE

NONE

WYE

DAC

WYE

DAC

WYE

NONE

DAB

WYE

DAB

WYE

WYE

NONE

DAC

WYE

DAC

WYE

WYE

NONE

ZAB

WYE

ZAB

WYE

WYE

NONE

BE1-11t