Basler Electric BE1-11t User Manual
Page 465
![background image](https://www.manualsdir.com/files/773775/content/doc465.png)
9424200995 Rev H
453
Turn-On Voltage
Contact-sensing turn-on voltages are listed in Table 205.
Table 205. Contact-Sensing Turn-On Voltages
Style Option
Nominal Input Voltage
Contact-Sensing Turn-On Voltage
*
Jumper Installed
(Low Position) †
Jumper Not Installed
(High Position) †
Txx1xxxxxxxxxx
48 Vdc or 125 Vac/dc
26 to 38 Vdc
69 to 100 Vdc
56 to 97 Vac
Txx2xxxxxxxxxx
125/250 Vac/dc
69 to 100 Vdc
56 to 97 Vac
138 to 200 Vdc
112 to 194 Vac
Txx3xxxxxxxxxx
24 Vdc
n/a
Approx. 5 Vdc
* AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (4 ms).
† Voltage ranges depend on jumper configurations. See the
chapter for more
information.
Input Burden
Burden values shown in Table 206 assume nominal value of input voltage applied.
Table 206. Contact-Sensing Input Burden
Style Option
Nominal Input Voltage
Burden
Jumper Installed
(Low Position)
Jumper Not Installed
(High Position)
Txx1xxxxxxxxxx
48 Vdc or 125 Vac/dc
22 k
Ω
53 k
Ω
Txx2xxxxxxxxxx
125/250 Vac/dc
66 k
Ω
123 k
Ω
Txx3xxxxxxxxxx
24 Vdc
n/a
6 k
Ω
Recognition Time
Programmable ........................................................... 4 to 255 ms
Note
All timing specifications are for the worst-case response. This includes
output contact operate times and standard BESTlogicPlus operation
timing but excludes input debounce timing and nonstandard logic
configurations. If a nonstandard logic scheme involves feedback, then
one or more BESTlogicPlus update rate delays must be included to
calculate the worst-case delay. An example of feedback is logic
outputs driving logic inputs. For more information, see BESTlogicPlus.
Terminals
IN1 ............................................................................. B1, B2
IN2 ............................................................................. B3, B4
IN3 ............................................................................. B5, B6
IN4 ............................................................................. B7, B8
IN5 ............................................................................. E1, E2
IN6 ............................................................................. E3, E4
IN7 ............................................................................. E5, E6
BE1-11t
Specifications