Page 479: Curve specifications, Time curve, Characteristics, Time, Curve characteristics

background image

9424200995 Rev H

467

Time Curve Characteristics

This chapter provides time curve information for the inverse overcurrent (51), under/overvoltage (27/59),
and overexcitation (24) functions of the BE1-11t.

Inverse Overcurrent (51)

General

The inverse overcurrent (51) time curves provided by the BE1-11t closely emulate most of the common
electromechanical, induction-disk, overcurrent relays sold in North America. To further improve proper
BE1-11t coordination, selection of integrated reset or instantaneous reset characteristics is also provided.

Curve Specifications

Timing Accuracy (All 51 Functions): Within ±5% or ±1½ cycles, whichever is greater, for time dial settings
greater than 0.1 and multiples of 2 to 40 times the pickup setting but not over 150 A for 5 A CT units or
30 A for 1 A CT units.

Twenty-two inverse time functions, one fixed time function, one 46 time function, one programmable time
function, and four Table Curve functions can be selected. Characteristic curves for the inverse and
definite time functions are defined by the following equations and comply with IEEE Std C37.112 - 1996 -
IEEE Standard Inverse-Time Characteristic Equations for Overcurrent Relays.

𝑇

𝑇

=

𝐴𝐷

𝑀

𝑁

− 𝐶 + 𝐵𝐷 + 𝐾

Equation 26

𝑇

𝑅

=

𝑅𝐷

|𝑀

2

− 1|

Equation 27

T

T

= Time to trip when M

≥ 1

T

R

= Time to reset if BE1-11t is set for integrating reset when M

< 1. Otherwise, reset is

50 milliseconds or less

D = Time Dial setting (0.0 to 9.9)

*

M = Multiple of Pickup setting (0 to 40)

A, B, C, N, K = Constants for the particular curve

R = Constant defining the reset time.

* Timing range is one second times the Time Dial setting when the F (fixed) curve is selected.

Table 207 lists time characteristic curve constants. See the figures after the tables for graphs of the
characteristics.

Table 207. 51 Time Characteristic Curve Constants

Curve

Selection

Curve Name

Trip Characteristic Constants

Reset

A

B

C

N

K

R

S1

CO Short Inverse

0.2663

0.03393

1

1.2969

0.028

0.5

S2

IAC Short Inverse

0.0286

0.0208

1

0.9844

0.028

0.094

A

Standard Inverse

0.01414

0

1

0.02

0.028

2

A1

IEC Inverse

0.14

0

1

0.02

0

20

BE1-11t

Time Curve Characteristics