0 (p.490), P.428) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 97

Configuring the Outer Control Loop
9-3
DIG
IN
0 (P.490)
Indicates the state of
digital input 0
(terminal 12 on the
Regulator board).
Parameter Range:
ON
OFF
(see table 9.2 for detail)
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
DIG
IN
0 is
ON
when +24VDC is applied for more than 10 msec. It is
OFF
when 0VDC
is applied.
Table 9.2 – Conditions Indicated by
DIG
IN
0 (P.490)
DIG
IN
0
SELECT
(P.428)
Setting
Condition if
DIG
IN
0 (P.490) Reads:
ON
OFF
BRUSH
WEAR
INPUT
OK
Worn
JOG
SPEED
SELECT
Jog Speed 2 active
Jog Speed 1 active
OCL
ENABLE
OCL
enabled
OCL
disabled
DIG
IN
0
SELECT
(P.428)
Determines which
function is controlled
by digital input 0
(terminal 12 on the
Regulator board).
Parameter Range:
1 =
BRUSH
WEAR
INPUT
2 =
JOG
SPEED
SELECT
3 =
OCL
ENABLE
Default Setting:
1
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
The signal can be:
•
OCL
ENABLE
: Enables the outer control loop if
CONTROL
SOURCE
SELECT
is not set
to
NETWORK
and if the I/O Expansion kit is not installed.
•
BRUSH
WEAR
: The input is from a brush wear indicator. If the input is
OFF
, the
MOTOR
BRUSH
WEAR
LOW
alarm is generated. You must have the E.S.P. Brush
Monitor Detector kit installed to use this option.
•
JOG
SPEED
SELECT
: The input determines whether
JOG
SPEED
1 (P.012) or
JOG
SPEED
2 (P.017) will be used when the drive is jogging.