P.103), P.192), 3 configuring the analog manual reference – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 26
![background image](/manuals/581746/26/background.png)
4-6
FlexPak 3000 DC Drive Software Reference
4.1.3 Configuring the Analog Manual Reference
CONTROL
SOURCE
SELECT
must be set to
TERMBLK
to use the analog manual reference
input as a speed reference. This reference can only be used when the drive is
configured as a speed regulator and
MANUAL
REF
SELECT
(P.106) is set to
ANALOG
.
When you use this speed reference, the drive uses the analog manual reference from
terminals 16(+10V), 17(+), and 18(–) of the Regulator board.
The software uses the parameters described in this section to scale the analog
manual reference signal at terminal 16, 17, and 18 to produce the
ANALOG
MAN
REFERENCE
(P.192) signal.
The analog manual reference input can also be used for the trim reference. Make sure
they are not being used for both functions at the same time.
AUTO
REFERENCE
SELECT
(P.103)
AUTO
REFERENCE
SELECT
determines if
the drive uses a
frequency or analog
input reference
source when the
drive is in
AUTO
mode
and
CONTROL
SOURCE
SELECT
is set to
KEYPAD
,
TERMBLK
, or
SERIAL
.
Parameter Range:
ANALOG
FREQUENCY
IN
Default Setting:
ANALOG
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
When
AUTO
REFERENCE
SELECT
is set to
FREQUENCY
IN
, the reference is from the
frequency input (terminals 39, 40, and 41 on the I/O Expansion kit).
When
AUTO
REFERENCE
SELECT
is set to
ANALOG
, the reference is from the analog
auto input (terminals 19 and 20 on the Regulator board).
If the I/O Expansion kit is not installed, this parameter is automatically configured to
ANALOG
and cannot be changed.
ANALOG
MAN
REFERENCE
(P.192)
The analog reference
value in manual
mode. This is the
value output by the
drive after all
hardware and
software scaling.
Parameter Range:
n/a
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Drive Reference - Drive Reference Scaling
Drive Reference - Drive Reference Test Points
This parameter is only used when the drive is configured as a speed/voltage
regulator.