P.004), P.003), P.018) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 40
![background image](/manuals/581746/40/background.png)
4-20
FlexPak 3000 DC Drive Software Reference
MAXIMUM
SPEED
(P.004)
The maximum speed
of the drive that can
be supported by the
application or
process.
Parameter Range:
1 to
TOP
SPEED
(
RPM
or user-defined units)
Default Setting:
500
RPM
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Limits
Quick Start
If raising this value causes
MINIMUM
SPEED
to become less than 10% of
MAXIMUM
SPEED
, an alarm is generated.
This is typically set to base speed from the motor nameplate.
!
ATTENTION: Do not allow the motor to exceed the maximum safe speed,
as determined by the equipment manufacturer, of the motor or the driven
equipment. Failure to observe this precaution could result in bodily injury.
MINIMUM
SPEED
(P.003)
Selects the minimum
speed of the drive
without being
stopped. It is typically
greater than zero.
Parameter Range:
0 to
MAXIMUM
SPEED
(
RPM
or user-defined units)
Default Setting:
250
RPM
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Limits
Quick Start
If it is less than 10% of
MAXIMUM
SPEED
, an alarm is generated.
!
ATTENTION: This drive can operate at and maintain zero speed when
this parameter is set to zero. The user is responsible for assuring safe
conditions for operating personnel by providing suitable guards, audible
or visual alarms, or other devices to indicate that the drive is operating
at or near zero speed. Failure to observe this precaution could result in
severe bodily injury or loss of life.
RAMP
STOP
DECEL
TIME
(P.018)
The deceleration time
used during ramp
stop sequences
when
STOP
DECEL
SELECT
is set to
RAMP
STOP
DECEL
TIME
.
Parameter Range:
0.1 to 300.0 seconds
Default Setting:
5.0 seconds
Parameter Type:
Tunable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
This parameter allows you to configure separate deceleration times for stopping
and decelerating.