P.418), P.419), P.422) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 125
![background image](/manuals/581746/125/background.png)
Configuring Parameters for the I/O Expansion Kit
11-9
ANLG
OUT
1
SELECT
(P.418)
Selects the signal
used to drive analog
output 1 (terminals
54 and 55 on the I/O
Expansion kit).
Parameter Range:
See table 11.1 for options
Default Setting:
ZERO
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Analog I/O
When the analog output is at its maximum value, the selected signal is at its full
scale value.
ANLG
OUT
1
SIG
TYPE
(P.419)
Selects the type of
signal to be
generated by analog
output 1 (terminals
54 and 55 on the I/O
Expansion kit).
Parameter Range:
0– 10 V
+/–10 V
4-20 mA
Default Setting:
+/–10 V
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Analog I/O
This setting must match the I/O Expansion kit J14 and J15 settings.
ANLG
OUT
2
GAIN
ADJ
(P.422)
Adjusts the gain of
analog output 2
(terminals 56 and 57
on the I/O Expansion
kit) to allow it to
produce a signal from
5.0 to the full scale
value of
approximately
13.0 VDC.
Parameter Range:
0.500 to 1.300
Default Setting:
1.000
Parameter Type:
Tunable
OIM Menu Path(s):
Input/Output - Analog I/O
The full scale value is determined by
ANLG
OUT
2
SELECT
. See table 11.1.
This is typically used to adjust the 10 V full scale output to match the input voltage
requirements of attached equipment. For example, set this parameter to 0.800 for
equipment that accepts a ±8 VDC signal.
The outputs are rated to 10 VDC, so gain adjust values greater than 1.000 might
cause the analog output circuit to saturate.
Analog output 2 only generates a ±10 VDC input signal and cannot be changed.
Analog output 1 and 2 are only rated to 10 VDC, so gain adjustment values greater
than 1.000 might cause the analog output circuit to saturate.