6-2
FlexPak 3000 DC Drive Software Reference
6.1
Configuring Inertia Compensation
INERTIA
COMP
SELECT
(P.221)
Selects the source of
the inertia
compensation signal.
The analog input
choices are only
available if the I/O
Expansion kit is
installed.
Parameter Range:
NONE
INTERNAL
ANALOG
IN
1
ANALOG
IN
2
NETW
IN
REG
1
NETW
IN
REG
2
NETW
IN
REG
3
Default Setting:
NONE
Parameter Type:
Configurable
OIM Menu Path(s):
Speed/Voltage Loop (
SPD
) - Speed/Voltage Loop
(
SPD
) Tuning
When
INTERNAL
is selected, the inertia compensation signal is generated by scaling
the rate output from the speed/voltage loop S-curve block based on the combined
inertia of the motor and its connected load.
Inertia compensation circuit supports constant diameter, constant field current
applications. The compensation signal is summed with the speed/voltage loop
PI
block output to form the reference to the
CML
.
When
INTERNAL
is selected, rate output from the speed/voltage loop S-curve block
is scaled based on the combined inertia of the motor and its connected load, as set
through the
NORMALIZED
INERTIA
(P.222).
A network kit must be installed to select the network input registers (
NETW
IN
REG
1,
2, or 3). Note that the network input registers are updated only when Control
Source (P.000) is set to
NETWORK
and the network is active.
MAXIMUM
CURRENT
(P.007)
The highest amount
of current (positive or
negative) for a given
application.
This input is the basis
of armature current
scaling.
Parameter Range:
25 to 200 %
FLA
Default Setting:
150 %
FLA
Parameter Type:
Configurable
OIM Menu Path(s):
Current Minor Loop (
CML
) -
CML
Feedback Scaling
MAXIMUM
CURRENT
is limited to 200% of
MOTOR
RATED
ARM
AMPS
.
The setting of
MAXIMUM
CURRENT
can affect the value of
J
18
ARM
I
FB
RESISTOR
(P.395). Check
J
18
ARM
I
FB
RESISTOR
(P.395) and the setting of the J18 jumper if
you change
MAXIMUM
CURRENT
.