Configuring the Current Minor Loop
6-3
6.2
Selecting and Conditioning CML Reference Selection
A hardware jumper, J15, configures the drive as a current/torque or speed/voltage
regulator. When J15 is set to
CURRENT
, the input signal
TORQUE
REFERENCE
(P.189) is
the
CML
reference.
TORQUE
REFERENCE
can come from an analog input, frequency
input, or a network master. When J15 is set to
SPEED
, the signal
SPD
LOOP
OUTPUT
(P.299) is the
CML
reference. The software reads the setting of hardware jumper J15
only at powerup. See the hardware manual for information on setting jumpers.
The selected
CML
reference passes through an amplitude limit block and a rate limit
block. See figure 6.1 for the block diagram.
The amplitude limit block prevents the reference signal from becoming greater than or
less than the limits selected by
CML
REF
LIMIT
SELECT
(P.311). These limits can be
either the values set by parameters
NEGATIVE
CURRENT
LIM
(P.006) and
POSITIVE
CURRENT
LIM
(P.005), or the limit values being used by the speed loop
PI
block.
The rate limit block limits the rate of change of the selected
CML
reference based on
value you input for
CML
REF
RATE
LIMIT
(P.303).
CML
REF
RATE
LIMIT
(P.303) defines the
minimum allowable time (in milliseconds) that the reference can change from zero to
MAXIMUM
CURRENT
(P.007). When the drive is stopped, the output of the rate limit block
is clamped to zero. The amplitude and rate-limited
CML
reference appears as the
output parameter
CML
REFERENCE
(P.396).
NORMALIZED
INERTIA
(P.222)
The time required to
accelerate the motor
and load inertia from
zero to motor base
speed at
MOTOR
RATED
ARM
VOLTS
(P.009) and
MOTOR
HOT
FLD
AMPS
(P.510).
Parameter Range:
0.05 to 65.20 seconds
Default Setting:
1.00 second
Parameter Type:
Tunable
OIM Menu Path(s):
Speed/Voltage Loop (SPD) - Speed/Voltage Loop
(SPD) Tuning
This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.
CML
REF
LIMIT
SELECT
(P.311)
Selects the source for
the
CML
positive and
negative current
limits.
Parameter Range:
1 =
SPD
LOOP
PI
LIMITS
2 =
REGISTER
Default Setting:
1
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
If you select
REGISTER
, the
CML
loop limits are
POSITIVE
CURRENT
LIM
(P.005) and
NEGATIVE
CURRENT
LIM
(P.006).
If you select
SPD
LOOP
PI
LIMITS
, the
CML
loop reference limits are the same as those
used by the speed loop
PI
block.