P.115), P.120), P.191) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 30: P.116)
4-10
FlexPak 3000 DC Drive Software Reference
MOP
ACCEL
TIME
(P.115)
Minimum time in
which
MOP
OUTPUT
can change from zero
to
TOP
SPEED
.
Parameter Range:
ACCELERATION
TIME
to 300.0 seconds
Default Setting:
5.0 seconds
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp
MOP
DECEL
TIME
(P.120)
Minimum time in
which
MOP
OUTPUT
can change from
TOP
SPEED
to zero.
Parameter Range:
DECELERATION
TIME
to 300.0 seconds
Default Setting:
5.0 seconds
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp
MOP
OUTPUT
(P.191)
The output of the
motor-operated
potentiometer (
MOP
).
Parameter Range:
MINIMUM
SPEED
to
MAXIMUM
SPEED
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Drive Reference - Drive Reference Test Points
To get a negative
MOP
reference, the reverse direction must be selected.
If the I/O Expansion kit is not installed,
MOP
OUTPUT
is meaningless.
MOP
RESET
ENABLE
(P.116)
Determines if
MOP
OUTPUT
(P.191) and
the keypad reference
values reset or stay
at the present level
when the drive stops.
Parameter Range:
OFF
ON
Default Setting:
OFF
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
When
MOP
RESET
ENABLE
is set to
ON
(enabled),
MOP
OUTPUT
and the keypad
reference are reset to
MINIMUM
SPEED
(P.003) when the drive is stopped, even if the
I/O Expansion kit is not installed. If it is set to
OFF
(disabled),
MOP
OUTPUT
and the
keypad reference remain at their present levels when the drive is stopped.