Configuring the Drive to Use Level Detectors
12-1
C
HAPTER
12
Configuring the Drive to Use
Level Detectors
The level detectors detect when the absolute value of a signal becomes greater than
or equal to a specified threshold for longer than a specified period. They can be used
as zero-speed detectors, at-speed detectors, or limit switches. They are used to drive
I/O Expansion kit digital output 1 or 2. To use the level detectors,
DIG
OUT
1
SELECT
(P.409) or
DIG
OUT
2
SELECT
(P.411) must be set to
LEVEL
DETECT
1
OUTPUT
or
LEVEL
DETECT
2
OUTPUT
. Level detector outputs can also be monitored over the AutoMax
network.
Figure 12.1 – Level Detectors Block Diagram
LEVEL
DETECT
1
DELAY
(P.604)
The delay time in
seconds for the level
detector 1 circuit.
Parameter Range:
0.0 to 300.0 seconds
Default Setting:
10.0 seconds
Parameter Type:
Tunable
OIM Menu Path(s):
Input/Output - Level Detectors
Sets the amount of time between when the level detector timer is triggered and
when the output is set
ON
. If the input source signal goes below the detector’s
threshold value, the timer is immediately reset.