P.101), P.100), P.102) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 25

Configuring the Speed Reference
4-5
ANLG
AUTO
GAIN
ADJ
(P.101)
Scales the analog
auto reference signal
after it is conditioned
by the drive
hardware.
Parameter Range:
0.750 to 1.250
Default Setting:
1.000
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Scaling
Typically, this parameter is set to 1.000.
Example
If
ANLG
AUTO
SIGNAL
TYPE
(P.100) is set to 0 -10V, a 0 to 8.2VDC signal produces
only 82% of the drive’s full scale value. To produce the drive’s full scale value,
change
ANLG
AUTO
GAIN
ADJ
to properly scale the signal to 1.22
.
Important: Adjust the zero point (
ANLG
AUTO
ZERO
ADJ
(P.102)) before setting the
gain adjust.
ANLG
AUTO
SIGNAL
TYPE
(P.100)
Selects the type of
signal applied to the
drive analog auto
reference input. This
is the signal at
terminals 19 and 20
on the Regulator
board.
Parameter Range:
0– 10V
+/–10V
4-20 mA
10-50mA
Default Setting:
0– 10V
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
Important: Jumpers J10 and J12 must be set for the type of analog auto reference
selected. See the hardware manual for instruction.
ANLG
AUTO
ZERO
ADJ
(P.102)
Removes any offset
from the analog auto
reference signal.
Parameter Range:
–200 to 200
Default Setting:
0
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Scaling
If
ANALOG
AUTO
REFERENCE
(P.188) is not equal to zero when the analog auto
reference signal is set to its minimum value (for example, 0 volts or 4mA), adjust
ANLG
AUTO
ZERO
ADJ
up or down until
ANALOG
AUTO
REFERENCE
(P.188) equals zero.
10
8.2
--------
1.22
=