5-20
FlexPak 3000 DC Drive Software Reference
5.7
Configuring Parameters for Winding Applications
These options are only available when using the AutoMax Network Communication
board (
CONTROL
SOURCE
SELECT
is set to
NETWORK
and
NETW
REGISTER
MAP
SEL
(P.914) is set to 2 (
ALTERNATE
)) or when using the ControlNet Network Communication
board.
For diameter-dependent loads, you can scale the feedback to the speed loop. The
feedback is scaled through a multiplier block. The operation of the multiplier block is:
Where:
•
A is a speed feedback multiplier (gain)
•
B is the speed feedback from the lead/lag block output
When
NETW
REGISTER
MAP
SEL
(P.914) is set to
ALTERNATE
, the source for A is the
network register
SPEED
FEEDBACK
GAIN
(alternate map, Drop_1, register 38). Even if
the multiplier block is not being used, you must write a value of 1000 to the
SPEED
FEEDBACK
GAIN
register whenever writing to Drop_1. This sets the multiplier block to
unity gain.
If the web is underwound, set
UNDERWIND
ENABLE
(alternate map, Drop_1, register 32,
bit 5) to
ENABLE
. This enables two inverters, one in the speed loop feedback path
immediately before the feedback summing junction, and one at the input to the
CML
limit block.
Refer to the appropriate network communication manual for register map
assignments.
A
B
•
1000
-------------