FlexPak 3000 DC Drive Software Reference
4.1.4 Configuring the Serial Speed Reference
CONTROL
SOURCE
SELECT
must be set to
SERIAL
(in the FlexPak 3000 drive or through
the CS3000 software) and
AUTO
/
MANUAL
must be set to
MANUAL
to use the serial
speed reference.
If you are using the serial reference from a source such as the CS3000 software, the
reference is input directly from the serial source to the speed reference ramp. The only
parameter related to the serial speed reference is
SPD
SOURCE
SELECT
OUT
(P.193).
You can use this parameter to check the reference value.
4.1.5 Configuring the Network Speed Reference
CONTROL
SOURCE
SELECT
must be set to
NETWORK
to use the network speed reference.
When the control source is
NETWORK
, the drive is forced into automatic mode.
The only parameter related to the network speed reference is
SPD
SOURCE
SELECT
OUT
(P.193). You can use this parameter to check the reference value.
4.1.6 Configuring the Motor-Operated Potentiometer (MOP) Reference
The
MOP
function can be used as a manual reference for the speed loop. To use the
MOP
function:
•
The I/O Expansion kit must be installed.
•
CONTROL
SOURCE
SELECT
must be set to
TERMBLK
.
•
MANUAL
REF
SELECT
(P.106) must be set to
MOP
.
•
Switches must be attached to digital inputs 3 and 4 (terminals 63 and 64) of the I/O
Expansion kit. These inputs decrement and increment, respectively, the
MOP
OUTPUT
(P.191) value.
•
The
MOP
block is shown in figure 4.3.
The
MOP
output is incremented when digital input 4 (terminal 63) is
ON
and
decremented when digital input 3 (terminal 62) is
ON
.
MOP
OUTPUT
is limited between
MAXIMUM
SPEED
(P.004) and
MINIMUM
SPEED
(P.003). If both digital inputs are
ON
at the
same time, the
MOP
output remains at its present value.
MOP
ACCEL
TIME
(P.115) and
MOP
DECEL
TIME
(P.120) set the time in which the
MOP
OUTPUT
can change from zero to
TOP
SPEED
and vice versa. To prevent the S-curve
block from limiting the rate of change from the
MOP
OUTPUT
,
MOP
ACCEL
TIME
has a low
limit equal to
ACCELERATION
TIME
.
MOP
DECEL
TIME
has a low limit equal to
DECELERATION
TIME
.
To obtain a negative
MOP
reference, the reverse direction must be selected.
When
MOP
RESET
ENABLE
is
ON
, the
MOP
output goes to
MINIMUM
SPEED
at the moment
when the drive is stopped following a run or jog. If it is
OFF
, the
MOP
OUTPUT
remains at
its present level when the drive is stopped.
MOP
RESET
ENABLE
also affects the
operation of the keypad reference, even if the I/O Expansion kit is not installed.