Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 140

13-8
FlexPak 3000 DC Drive Software Reference
F00700
FACTORY
DEFAULTS
RESTORED
The stored parameter values were determined to be invalid. Factory
default values have been restored. All parameter values (including any
factory set parameters) must be re-adjusted based on your application
before operating the drive. After all parameters have been set properly, a
memory save must be performed followed by a fault reset.
Possible causes:
•
Power loss during a prior memory save.
•
New Regulator board.
•
Defective Regulator board.
F00701
FAULT
LOG
RESTORE
FAILURE
The fault log information stored in retentive memory was determined to be
invalid. The fault log has been cleared.
Possible causes:
•
Power loss during a prior fault log save.
•
Defective Regulator board.
F00702
KEYPAD
REF
RESTORE
FAILURE
The keypad reference value stored in retentive memory was determined to
be invalid. The keypad reference has been set to the
MINIMUM
SPEED
(P.003) value.
Possible causes:
•
Power loss during a previous keypad reference save.
•
Defective Regulator board.
F00703
OIM
KEY
RESTORE
FAILURE
The
OIM
key states stored in retentive memory are invalid. The
FORWARD
/
REVERSE
key has been set to
FORWARD
and the
AUTO
/
MANUAL
key
has been set to
MANUAL
.
It is possible to get this fault on a drive equipped with a
DCM
. If so, replace
the Regulator board.
Possible cause: Defective Regulator board.
F00800
INVALID
FIELD
INSTALLED
Installed field supply is not supported by the regulator.
Possible causes:
•
Disconnected, loosely connected, or damaged field supply wires.
•
Regulated field supply failure.
•
Regulator board failure.
F00801
FIELD
FEEDBACK
OFFSET
TOO
HIGH
Regulated field supply feedback offset is too high.
Possible causes:
•
Disconnected, loosely connected, or damaged field supply wires.
•
Regulated field supply failure.
•
Regulator board failure.