Configuring Parameters for the I/O Expansion Kit
11-3
DIG
OUT
1
SELECT
(P.409)
Selects the signal
that drives digital
output 1 (terminals
66 and 67 on the I/O
Expansion kit).
Parameter Range:
LEVEL
DETECT
1
OUTPUT
LEVEL
DETECT
2
OUTPUT
IN
CURRENT
LIMIT
DRIVE
READY
NETW
COMM
STATUS
NETW
IN
REG
1 (bit 0)
NETW
IN
REG
2 (bit 0)
NETW
IN
REG
3 (bit 0)
Default Setting:
LEVEL
DETECT
1
OUTPUT
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Digital I/O
•
LEVEL
DETECT
1 or 2
OUTPUT
: The state of the selected level detector output is
used to drive digital output 1. The signal is from the I/O Expansion kit digital
output 1 or 2. See chapter 12, Configuring the Drive to Use Level Detectors.
•
IN
CURRENT
LIMIT
: The armature in-current-limit signal is used to drive digital
output 1. The in-current-limit signal indicates whether or not the drive is operating
at the maximum allowable current. See
CML
REF
LIMIT
SELECT
(P.311).
•
DRIVE
READY
: The drive-is-ready signal is used to drive digital output 1. The
drive-is-ready signal indicates that the drive will start when the next run or jog
command is received.
•
NETW
COMM
STATUS
: The state of
NETW
COMM
STATUS
(P.908) is used to drive
digital output 1. See chapter 10 for description.
•
NETW
IN
REG
1, 2, or 3: Bit 0 of
NETW
IN
REG
1 (P.905), 2 (P.906), or 3 (P.907) is
used to drive digital output 1. A network kit must be installed to select the network
input registers. Note that the network input registers are updated only when
Control Source (P.000) is set to
NETWORK
and the network is active. See chapter
10 for description.
DIG
OUT
2
CONTACT
TYP
(P.412)
Selects whether
digital output 2
(terminals 68 and 69
on the I/O Expansion
kit) is normally open
or normally closed.
Parameter Range:
NORMAL
OPEN
NORMAL
CLOSED
Default Setting:
NORMAL
OPEN
Parameter Type:
Configurable
OIM Menu Path(s):
Input/Output - Digital I/O
If
NORMAL
OPEN
is selected, digital output 2 is open when the signal selected by
DIG
OUT
2
SELECT
(P.411) is off and closed when it is on.
If
NORMAL
CLOSED
is selected, digital output 2 is closed when the signal selected by
DIG
OUT
2
SELECT
(P.411) is off and open when it is on.
!
ATTENTION: On a power cycle or reset, the contact is held open until the
drive software powerup diagnostics are complete. Make sure this condition
does not result in a dangerous situation for your application. Failure to
observe this precaution can result in severe bodily injury or loss of life.