P.303), P.396), P.226) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 74
![background image](/manuals/581746/74/background.png)
6-4
FlexPak 3000 DC Drive Software Reference
CML
REF
RATE
LIMIT
(P.303)
Minimum time for
CML
REFERENCE
to change
from zero to
MAXIMUM
CURRENT
.
Parameter Range:
1 to 1000 msec
Default Setting:
40 msec
Parameter Type:
Tunable
OIM Menu Path(s):
Current Minor Loop (
CML
) -
CML
Tuning
This parameter is set by the
CML
self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.
CML
REFERENCE
(P.396)
The amplitude and
rate limited value of
the selected
CML
reference.
Parameter Range:
n/a
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Current Minor Loop (
CML
) -
CML
Test Points
NEG
CUR
LIM
INV
EN
(P.226)
Enables or disables
the negative current
limit inverter to the
speed loop
PI
block
low limit input.
Parameter Range:
DISABLED
ENABLED
Default Setting:
ENABLED
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
When this parameter is set to
ENABLED
,
POSITIVE
CURRENT
LIM
(P.005) and
NEGATIVE
CURRENT
LIM
(P.006) are restricted to positive values.
When this parameter is set to
DISABLED
, the range of
NEGATIVE
CURRENT
LIM
(P.006)
is restricted to negative values.
When you change this parameter value:
•
Alarm A00052 occurs.
•
The parameters
NEG
CURRENT
LIM
SEL
(P.224) and
POS
CURRENT
LIM
SEL
(P.223)
are automatically set to
REGISTER
.
•
The value of
NEGATIVE
CURRENT
LIM
(P.006) is inverted. For example, if
NEG
CUR
LIM
INV
EN
is set to
ENABLE
and
NEGATIVE
CURRENT
LIM
is set to 150%
FLA
,
changing
NEG
CUR
LIM
INV
EN
to
DISABLED
causes the value of
NEGATIVE
CURRENT
LIM
to change to –150%
FLA
.
Carefully check your current limit scheme and the values of
POSITIVE
CURRENT
LIM
(P.005) and
NEGATIVE
CURRENT
LIM
(P.006) to avoid unintended drive operation.