Troubleshooting the FlexPak 3000 Drive
13-7
F00065
SELF
TUNING
FAULT
Speed unstable.
Possible causes:
•
CML
not properly tuned before speed loop.
•
Tachometer or encoder feedback device connected incorrectly.
F00066
SELF
TUNING
FAULT
SELF
TUNE
STABILITY
(P.219) is too low.
Possible causes:
•
Specified stability is less than that calculated by
CML
self-tuning. Use 50
or more.
F00067
SELF
TUNING
FAULT
SELF
TUNE
STABILITY
(P.219) is too low.
Possible causes:
•
Specified stability is less than that calculated by
CML
self-tuning. Use 75
or more.
F00089 to
F00099
SELF
TUNING
FAULT
Fatal self-tuning fault occurred.
Possible cause:
•
Self-tuning was unable to complete. Tune manually.
F00100
MAIN
CONTACTOR
DID
NOT
OPEN
The main (
FN
) contactor did not open following a run or jog request. If a
dynamic braking kit is used, the dynamic braking auxiliary contact is wired
in series with the
FN
auxiliary contact.
Possible causes:
•
Disconnected, loosely connected, or damaged
FN
,
FN
auxiliary, dynamic
braking, or dynamic braking auxiliary wiring.
•
FN
,
FN
auxiliary, dynamic braking, or dynamic braking auxiliary contactor
failure.
•
Disconnected, loosely connected, or damaged main contactor or
dynamic braking control wiring (
MCR
or
DBCR
).
F00200
POWER
FAILURE
The power supply input voltage momentarily went below tolerance.
Possible causes:
•
AC line voltage dip.
•
Disconnected, loosely connected, or damaged J7 ribbon cable or power
supply input wiring
Table 13.1 – Fault Codes (Continued)
Code
OIM Display
Description