FlexPak 3000 DC Drive Software Reference
DIG
IN
2 (P.496)
The state of digital
input 2 (terminal 60
on the I/O Expansion
kit).
Parameter Range:
ON
OFF
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Input/Output - Digital I/O
Digital inputs 1 and 2 (terminals 59 and 60) select which, if any, preset speed is
used as the reference for the speed/voltage control loop.
The input is
ON
when +24 VDC is applied for more than 10 msec. It is
OFF
when
0 VDC is applied.
PRESET
SPEED
1 (P.117)
PRESET
SPEED
2 (P.118)
PRESET
SPEED
3 (P.119)
These parameters
set up to three preset
speed references
when the
REGULATOR
TYPE
jumper (J15 on
the Regulator board)
is set for the
speed/voltage control
loop.
Parameter Range:
MINIMUM
SPEED
to
MAXIMUM
SPEED
(
RPM
or
user-defined units)
Default Setting:
250
RPM
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
To use these speeds,
CONTROL
SOURCE
SELECT
must be set to
TERMBLK
.
The preset speeds are selected through digital input 1 and digital input 2 on the I/O
Expansion kit, as shown in table 4.2.
If the I/O Expansion kit is not installed, the digital inputs are set to
OFF
and cannot
be changed. The selected auto or manual reference is used for the reference.
The preset speed reference passes through the same control blocks as other
speed references.