Configuring the Speed Reference
4-19
AUTO
MODE
RAMP
BYPASS
(P.112)
Bypasses the speed
loop S-curve block
while in auto mode. If
the drive is in manual
mode, this parameter
has no effect and the
S-curve block cannot
be bypassed.
Parameter Range:
OFF
ON
Default Setting:
OFF
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp
When
AUTO
RAMP
BYPASS
is
ON
and the drive is in auto mode, the speed loop ramp
function is bypassed. The bypass is automatically disabled during a ramp stop
sequence and the drive will always ramp to a stop.
!
ATTENTION: When switching from auto to manual or from manual to
auto, the drive will ramp to the reference level provided by the new source
at the rate specified by
ACCELERATION
TIME
(P.001) or
DECELERATION
TIME
(P.002). Be aware that an abrupt speed change might occur, depending
on the new reference and the rate specified in these parameters. Failure
to observe this precaution could result in bodily injury.
DECELERATION
TIME
(P.002)
Sets the minimum
time in which the
selected speed
reference can change
from
TOP
SPEED
(P.011) to 0.
Parameter Range:
0.1 to 300.0 seconds
Default Setting:
5.0 seconds
Parameter Type:
Tunable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp
Quick Start
If
TRIM
MODE
SELECT
(P.110) is set to
PROPORTIONAL
, the actual time to decelerate
might be modified by
DRAW
PERCENTAGE
OUT
(P.196). See section 4.2, Configuring
Trim.