Configuring the Enhanced Field Supply
These parameters are available only if the Enhanced Field Supply kit is installed.
ENHANCED
FLD
VOLT
ADJ
(P.500)
Adjusts the field
output voltage.
ENHANCED
FLD
VOLT
ADJ
has no effect on
the operation of the
standard field supply
or the Field Current
Regulator kit.
Parameter Range:
0 to 180 (J21 set to B-C)
0 to 120 (J21 set to A-C)
Default Setting:
84
0 when the Field Current Regulator kit is installed
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Standard/enhanced Field Supply
Increasing
ENHANCED
FLD
VOLT
ADJ
increases the output voltage at the F1 and F2
terminals. Decreasing
ENHANCED
FLD
VOLT
ADJ
decreases the output voltage.
ENHANCED
FLD
VOLT
ADJ
has no effect when the drive is in field economy (
FIELD
ECONOMY
ACTIVE
(P.599) reads
ON
).
See the Enhanced Field Supply kit manual for detail on setting this jumper.
J20
FIELD
LOSS
DETECT
(P.597)
Indicates the position
of jumper J20,
FIELD
LOSS
DETECT
, which
enables or disables
field current loss
detection. This
jumper is only read
on powerup.
Parameter Range:
ENABLE
DISABLE
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Drive Information
Field - Standard/enhanced Field Supply
J20 should only be set to the
DISABLE
position when an external field supply is used.
Important: Jumper J20 is ignored if the Field Current Regulator kit is installed.
Therefore, placing J20 in the
DISABLE
position will not disable field loss
detection. See manual D2-3336 for information on the Field Current
Regulator kit.
!
ATTENTION: The user must provide external field current loss detection
and inhibit drive operation using one of the drive interlocks when this
jumper is positioned to
DISABLE
. Misapplication of this jumper can cause
the motor to run at dangerously high speeds. Provide external field
current loss detection and inhibit drive operation using one of the drive
interlocks if this jumper is positioned to
DISABLE
. Failure to observe this
precaution could result in bodily injury.