3 configuring parameters for the automax network, P.911), P.914) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 114
10-8
FlexPak 3000 DC Drive Software Reference
10.3 Configuring Parameters for the AutoMax Network
These parameters are only available if the AutoMax Network Communication board is
installed. For more information on the board and parameters, see the AutoMax
Network Communication board manual (D2-3318).
AMX
NETW
REF
SELECT
(P.911)
AutoMax Network
reference selection.
Parameter Range:
DIRECT
BROADCAST
n
where n = 1 to 8
Default Setting:
DIRECT
Parameter Type:
Configurable
OIM Menu Path(s):
Network Communications
Selects whether the drive reference is from the designated register in the drop
register image or from one of the eight network broadcast registers when
CONTROL
SOURCE
SELECT
is set to
NETWORK
.
NETW
REGISTER
MAP
SEL
(P.914)
Indicates which
register map
configuration will be
used for the AutoMax
Network
Communication kit.
Parameter Range:
1 =
ORIGINAL
2 =
ALTERNATE
Default Setting:
1
Parameter Type:
Configurable
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
ALTERNATE
selects the new register map, which permits use of additional functions.
ORIGINAL
should be used if you need to maintain compatibility with older FlexPak
drives that do not have a selectable register map (V3.12 and earlier).