P.212), P.211) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 67
Configuring the Speed/Voltage Loop
5-19
SPD
LOOP
PI
LEAD
FREQ
(P.212)
Speed loop
PI
block
lead break frequency.
Parameter Range:
0.00 to 282.74
RAD
/
S
when
•
FEEDBACK
SELECT
(P.200) =
ARMATURE
VOLT
•
SPD
LOOP
SCAN
TIME
(P.019) = 10
MS
0.00 to 327.67
RAD
/
S
when
•
FEEDBACK
SELECT
(P.200)
≠
ARMATURE
VOLT
•
SPD
LOOP
SCAN
TIME
(P.019) = 5
MS
Default Setting:
3.00
RAD
/
S
Parameter Type:
Tunable
OIM Menu Path(s):
Speed/Voltage Loop (
SPD
) - Speed/Voltage Loop
(
SPD
) Tuning
A setting of 0.00 allows proportional-only speed loop control.
This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.
SPD
LOOP
PI
PROP
GAIN
(P.211)
Speed loop PI block
proportional gain.
Parameter Range:
0.10 to 128.00
Default Setting:
4.40
Parameter Type:
Tunable
OIM Menu Path(s):
Speed/Voltage Loop (
SPD
) - Speed/Voltage Loop
(
SPD
) - Tuning
This parameter is set by the speed loop self-tuning procedure. You can also enter it
directly. Self-tuning will overwrite values entered manually.
SPD
LOOP
PI
RESET
While this is
ON
, the
speed loop
PI
block is
held in reset and the
block’s output is the
initial value selected
by
SPD
LOOP
PI
INIT
VAL
(Drop_1, register
39 of the alternate
network register
map).
Parameter Range:
0 =
OFF
1 =
ON
Default Setting:
0
Parameter Type:
Tunable
OIM Menu Path(s):
This parameter is only available over the network. It
cannot be viewed through the
OIM
.
SPD
LOOP
PI
RESET
is forced
OFF
when
CONTROL
SOURCE
SELECT
is not
NETWORK
.
Refer to the appropriate network communication manual for register map
assignments.