P.517), P.587), P.512) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 93
Configuring the Field Supply
8-9
FIELD
AUTO
WEAKEN
(P.517)
Enables or disables
automatic field
weakening by the
field control loop.
When it is disabled,
the field current
PI
block high limit is
fixed at 180 degrees.
Parameter Range:
DISABLED
ENABLED
Default Setting:
DISABLED
Parameter Type:
Configurable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Configure
If
FEEDBACK
SELECT
is set to
ARMATURE
VOLT
, this is automatically set to
DISABLED
and cannot be changed.
FIELD
DELTA
HIGH
LIM
(P.587)
High limit of the field
current
PI
block.
Parameter Range:
0 to 180
DEGREE
Default Setting:
130
DEGREE
Parameter Type:
Configurable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Configure
FIELD
LOSS
THRESHOLD
(P.512)
The value that is
compared to
FIELD
FEEDBACK
(P.589) to
check for field loss.
Parameter Range:
50 to 100% of
MOTOR
HOT
FLD
AMPS
(P.510) when
FEEDBACK
SELECT
(P.200) is set to
ARMATURE
VOLT
0 to 100% of
MOTOR
HOT
FLD
AMPS
(P.510) when
FEEDBACK
SELECT
(P.200) is set to
DC
TACH
,
PULSE
TACH
, or
AC
TACH
Default Setting:
60% of
MOTOR
HOT
FLD
AMPS
(P.510)
Parameter Type:
Configurable
OIM Menu Path(s):
Field – Field Current Regulator – Field Loop
Configure
FIELD
LOSS
THRESHOLD
is set as a percentage of
MOTOR
HOT
FLD
AMPS
. It is usually
set to 85% of the motor nameplate field weaken current.