P.501), P.511), P.513) – Rockwell Automation FlexPak 3000 Digital DC Drive Version 4.3 User Manual
Page 87

Configuring the Field Supply
8-3
FIELD
ECONOMY
DELAY
(P.501)
After the motor stops,
the drive maintains
full field for
FIELD
ECONOMY
DELAY
minutes before
entering field
economy.
Parameter Range:
0 to 27 minutes
Default Setting:
5 minutes
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Standard/enhanced Field Supply
Field - Field Current Regulator - Field Loop Configure
When the motor starts again, the drive immediately returns to full field.
FIELD
ECONOMY
DELAY
does not affect operation of the standard field supply. Field
economy cannot be disabled.
This parameter has no effect when the Enhanced Field Supply kit or standard field
supply is installed.
FIELD
ECONOMY
REF
(P.511)
Only available if the
Field Current
Regulator kit is
installed.
Parameter Range:
0 to 100%
Default Setting:
0%
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Configure
The percentage of
MOTOR
HOT
FLD
AMPS
(P.510) set as a reference for field
economy mode. This parameter must be set above the
FIELD
LOSS
THRESHOLD
(P.512) value to avoid field loss faults.
This parameter has no effect when the Enhanced Field Supply kit or standard field
supply is installed.
FIELD
REF
REGISTER
(P.513)
Current reference for
the field control loop.
This is the field
current reference
when the drive is not
in field economy.
Parameter Range:
0 to
MOTOR
HOT
FLD
AMPS
Default Setting:
MOTOR
HOT
FLD
AMPS
Parameter Type:
Tunable
OIM Menu Path(s):
Field - Field Current Regulator - Field Loop Tuning
FIELD
REF
REGISTER
should be set greater than
FIELD
LOSS
THRESHOLD
(P.512) to
avoid
FIELD
LOSS
faults.
Only available if the Field Current Regulator kit is installed.