Configuring the Speed Reference
4-25
4.4.1 Configuring Jog
For information on jog sequencing, see section 2.1, Run and Jog Sequencing.
When you use a jog input (terminals 4 and 1 on the Regulator board or pressing
), the jog signal is conditioned as shown in figure 4.7.
If
DIG
IN
0
SELECT
(P.428) is set to
JOG
SPEED
SELECT
, you can use digital input 0
(terminals 12 and 14 on the Regulator board) to choose between two jog speeds, as
set by
JOG
SPEED
1 (P.012) and
JOG
SPEED
2 (P.017).
When digital input 0 is:
•
Off (0 V):
JOG
SPEED
1 (P.012) is selected.
•
On (+24 V):
JOG
SPEED
2 (P.017) is selected.
Switching between the two jog speeds while jogging causes the drive to accelerate or
decelerate to the new jog speed at the rate set by
JOG
ACCEL
/
DECEL
TIME
(P.013).
Only
JOG
SPEED
1 (P.012) is used if
DIG
IN
0
SELECT
is not set to
JOG
SPEED
SELECT
.
!
ATTENTION: This drive can operate at and maintain zero speed when
either of the jog speed parameters (
JOG
SPEED
1 (P.012) and
JOG
SPEED
2
(P.017)) is set to zero. The user is responsible for assuring safe conditions
for operating personnel by providing suitable guards, audible or visual
alarms, or other devices to indicate that the drive is operating at or near
zero speed. Failure to observe this precaution could result in severe
bodily injury or loss of life.
DIG
IN
0 (P.490)
Indicates the state of
digital input 0
(terminal 12 on the
Regulator board).
Parameter Range:
ON
OFF
(see table 4.3 for detail)
Default Setting:
n/a
Parameter Type:
Output
OIM Menu Path(s):
Additional Parameters (listed by parameter number)
DIG
IN
0 is
ON
when +24VDC is applied for more than 10 msec. It is
OFF
when 0VDC
is applied.
Table 4.3 – Conditions Indicated by
DIG
IN
0 (P.490)
DIG
IN
0
SELECT
(P.428)
Setting
Condition if
DIG
IN
0 (P.490) Reads:
ON
OFF
BRUSH
WEAR
INPUT
Brushes OK
Brushes Worn
JOG
SPEED
SELECT
JOG
SPEED
2 selected
JOG
SPEED
1 selected
OCL
ENABLE
OCL
enabled
OCL
disabled