Field supply configuration – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 80

4–8
Start–Up and Adjustment
Publication 1397-5.0 — June, 2001
Verify which shunt field supply has shipped with your Drive.
Configuration procedures will vary depending on field supply type.
!
ATTENTION: Field Supply configuration must be
checked while making the Pre-Power Checks. If your
Drive uses either the optional Enhanced Field Supply
or the Regulated Field Supply, different configuration
procedures are required than with the Standard Field
Supply. Power should not be applied to the motor field
windings prior to adjusting these parameters, as
outlined in the respective field supply’s installation
manual. Failure to properly configure your field
supply could cause the motor to run at excessive speed
or damage the motor which could result in personal
injury or destruction of equipment.
Standard Field Supply (See Note Below)
If the Standard Field Supply (Fig. 4.4) is installed, adjustment is not
necessary.
AC
SP3
SP4
LINE CT
582
583
581
F1/37
F1/35
N/P(610273-14R)
SP1
SP2
AC
+
–
AC
X1
X2
H2
H1
Figure 4.4
Standard Field Supply Terminations
Note: Regulated Field Supply is provided as standard on:
230V Drives with ratings above 45 kW (60 Hp)
460V Drives with ratings above 112 kW (150 Hp)
380/415V Drives with ratings above 35.8 kW (48 Hp)
Field Supply Configuration