Figure 2.22 terminal strip inputs – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 50

2–32
Installation
Publication 1397-5.0 — June, 2001
TB–03
STOP – This is a level sensitive signal that initiates a
Stop command (0 = Stop, 1 = Not Stop). The stopping
mode is determined by the [Stop Mode Type] (P. 115)
parameter. This input CANNOT be masked. Both the
customer interlock And Coast to Stop must be made for
the Drive to be READY.
Figure 2.22
Terminal Strip Inputs
Regulator Board Terminal Strip Inputs
20
1
REV
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
ANLG REF 1
ANLG REF 2
21
22
23
+24V
Run
Stop
Jog
Reverse/Forward
Reference Select
+24V
Customer Interlock
Fault Alarm Reset
+24V
Brush Wear
Motor Thermostat
+24V
+24V Common
+10V (Isolated)
+
–
+
–
High Range
Low Range
Common
Coast-to-Stop
Analog Reference 2
Analog Tachometer In
PLC End
(Refer to Pub. 1397-5.0 for Additional Information)
Regulator Board Terminal Strip Software Configurable Output Connections
(Drive Contacts Shown In Unpowered State)
24
25
26
27
28
29
30
31
32
Analog Out 1
Analog Out Common
Analog Out 2
Run
Fault
Alarm
FWD
2
3
2> All customer interlock contacts
must be closed for drive operation.
3> The circuit breaker is supplied with
200-300 HP regenerative drives.
Note that if any other interlocks are
required for your application, they
must be connected in series with
the circuit breaker contact to the
customer interlock input.
*
*
*
*
*
*
*
*
*
*
*
*
= Required for initial startup and
operational checks.
Voltage must be present at these
points during operation.
Analog Reference 1
RUN/STOP
by user
contact
1
2
3
Analog Reference 2
24V Common