Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 14

1–6
Introduction
Publication 1397-5.0 — June, 2001
Full Load Rated
RMS AC Line
Current (Amperes)
Full Load Rated
DC Armature
Current (Amperes)
Rated Field Current
(Amperes)
Power Source
Capacity
1
(Amperes)
Minimum
Source
HP
230 V AC
460 V AC
240 V DC
500 V DC
150 V DC
300 V DC
230 V AC
460 V AC
Source
kVA
1.5
10
-
7
-
10
-
5000
-
4
2
11
-
9
-
10
-
5000
-
5
3
13
10
12
6
10
10
5000
5000
6
5
19
12
20
10
10
10
5000
5000
7.5
7.5
26
15
29
14
10
10
5000
5000
11
10
33
18
38
19
10
10
5000
5000
15
15
48
24
55
27
10
10
5000
5000
20
20
63
31
73
35
15
10
10000
5000
27
25
80
39
93
45
15
10
10000
5000
34
30
94
45
110
52
15
10
10000
5000
40
40
125
63
146
73
15
15
25000
10000
51
50
154
74
180
86
15
15
25000
10000
63
60
186
86
218
100
15
15
25000
10000
75
75
226
110
265
129
15
15
25000
25000
93
100
307
143
360
167
15
25000
118
125
370
177
434
207
15
25000
145
150
443
213
521
250
15
25000
175
200
281
330
15
30000
220
250
351
412
15
30000
275
300
421
495
15
30000
330
400
567
667
15
75000
440
500
680
800
15
75000
550
600
816
960
15
75000
660
ATTENTION: When applying 1397 Drives to a power distribution system with KVA capacity in excess of five times the smallest
drive rating the use of an isolation transformer or line reactors of similar impedance is required. Also, the Drives are designed
for a maximum of three units per transformer.
1 Maximum permissible available symmetrical RMS fault current.
380 VAC
KW/HP
415 VAC
KW/HP
380/415
Full Load Rated
RMS AC Line
Current Amperes
380/415
Full Load Rated
DC Armature
Current Amperes
Rated
Field
Current
Power
Source
Capacity
(Amperes)
1.8/2.4
2.1/2.8
10
7
10
5,000
9/12
10.3/13.6
26
29
10
5,000
17.9/24
20.6/27.6
48
55
10
5,700
35.8/48
41.2/55.2
94
110
15
11,500
89.5/120
102.9/138
226
265
15
25,000
Power Ratings and Supply
Capacity (230/460VAC)
Power Ratings and Supply
Capacity (380/415VAC)