Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual
Page 128
5–18
Programming Parameters
Publication 1397-5.0 — June, 2001
METERING
[OCL Enable TP] — P.016
The status of the outer control loop (OCL). Off
indicates the OCL is disabled or held in reset
(the drive is not running). On (Enabled)
means it is operating.
Display/Drive Units:
Enum Text
Group:
Metering
Type:
Read Only
Factory Default:
0
Minimum Value:
0 (Disabled)
Maximum Value:
1 (Enabled)
[OCL Feedback] — P.017
The feedback value of the outer control loop.
Refer to the [Outer Control Loop] (Fig. A.5)
block diagram for additional information.
Display/Drive Units:
CNTS
Group:
Metering
Factory Default:
0
Minimum Value:
–5120
Maximum Value:
5120
[OCL Output] — P.018
The output of the outer control loop in speed
units. This is the OCL trim that is applied to
the speed/voltage control loop. Refer to the
[Outer Control Loop] block diagram (Fig.
A.5) for additional information.
Display/Drive Units:
RPM
Group:
Metering
Factory Default:
0
Minimum Value:
–5000
Maximum Value:
5000
[OCL Ramp Output] — P.019
The outer control loop reference ramp output
in OCL user units. This is the OCL reference
output after OCL reference rounding and
S-curve have been applied. Refer to the
[OCL Ramp Time] block diagram for
additional information.
Display/Drive Units:
CNTS
Group:
Metering
Factory Default:
0
Minimum Value:
–4095
Maximum Value:
4095
[OCL Reference TP] — P.020
The value of the currently selected OCL
Reference Source.
Display/Drive Units:
CNTS
Parameter Type:
Read Only
Group:
Metering
Factory Default:
0
Minimum Value:
–4095
Maximum Value:
4095