CE Conformity

B–4

Publication 1397-5.0 — June, 2001

Mount all electronic and electromagnetic components, including the
Drive and the line filter, firmly to the base mounting panel. The
mounting panel must have good conductivity, as described in the
paragraph Selecting a Mounting Panel and Electrical Cabinet.

Mounting the Drive– If the cabinet includes ventilation louvers or
filter and fan openings in the sides or door, the openings cannot be
located within a zone 254 mm (10 inches) above and below the
height of the Drive as shown in Figure B.1.

Figure B.1
Prohibited Area for Cabinet Ventilation Openings

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗ

No cabinet openings in
the doors or sides are
permitted in the shaded
area.

254mm
(10 in)

254mm
(10 in)

Mounting the AC Line Filter – Refer to Figures B.2 and B.3 for
filter mounting dimensions. The filter can be mounted either flat,
with its back against the panel, or on its side, with either side against
the panel. If the 3DF4359 is mounted on its side, it must be mounted
on the L bracket (included with the filter). Mount the 3DF4359 in
the L bracket first, then mount the L bracket using 12mm screws.

Mounting the Equipment