Programming and Parameters

3-53

Enhanced Program Group

(continued)

E209 [Half Bus Enable]

Enables/disables the power ride through function which allows the drive to maintain power to the
motor at 50% drive input voltage during short-term power sag conditions.

Options

0 “Disabled” (Default)

1 “Enabled”

!

ATTENTION:

To guard against drive damage, a minimum line

impedance must be provided to limit inrush current when the power line
recovers. The input impedance should be equal or greater than the
equivalent of a 5% transformer with a VA rating 6 times the drive’s input VA
rating.

E210 [Max Traverse]

Related Parameter(s):

E211

,

E212

,

E213

Sets the amplitude of triangle wave speed modulation.

Values

Default:

0.00 Hz (Disabled)

Min/Max:

0.00/300.0 Hz

Display:

0.01 Hz

Hertz

Seconds

Traverse Bit

212 [Traverse Dec]

211 [Traverse Inc]

Traverse Enable Bit

d302 [Fiber Status]

b001 [Output Freq]

E213 [P Jump]

E210 [Max Traverse]

E213 [P Jump]

E211 [Traverse Inc]

Related Parameter(s):

E210

Sets time required for the Traverse function to accelerate from the minimum to the maximum traverse
frequency. Refer to the diagram at

E210

[Max Traverse].

Values

Default:

0.00 Secs

Min/Max:

0.00/30.00 Secs

Display:

0.01 Secs