Advanced Program Group
(continued)
A064 [Opto Out Logic]
Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto outputs.
Values
Default:
0
Min/Max:
0/3
Display:
1
A064 Option
Opto Out1 Logic
Opto Out2 Logic
0
1
2
3
NO (Normally Open)
NC (Normally Closed)
NO (Normally Open)
NC (Normally Closed)
NO (Normally Open)
NO (Normally Open)
NC (Normally Closed)
NC (Normally Closed)
A065 [Analog Out Sel]
Related Parameter(s):
Sets the analog output signal mode (0-10V, 0-20mA, or 4-20mA). The output is used to provide a
signal that is proportional to several drive conditions.
Values
Default:
0
Min/Max:
0/20
Display:
1
Option
Output
Range
Minimum Output
Value
Maximum Output Value
A066 [Analog Out High]
DIP Switch
Position
Related
Parameter
0 “OutFreq 0-10”
0-10V
0V = 0 Hz
P035 [Maximum Freq]
0-10V
1 “OutCurr 0-10”
0-10V
0V = 0 Amps
200% Drive Rated Output Current
0-10V
2 “OutVolt 0-10”
0-10V
0V = 0 Volts
120% Drive Rated Output Volts
0-10V
3 “OutPowr 0-10”
0-10V
0V = 0 kW
200% Drive Rated Power
0-10V
4 “TstData 0-10”
0-10V
0V = 0000
65535 (Hex FFFF)
0-10V
5 “OutFreq 0-20”
0-20mA
0 mA = 0 Hz
P035 [Maximum Freq]
0-20mA
6 “OutCurr 0-20”
0-20mA
0 mA = 0 Amps
200% Drive Rated Output Current
0-20mA
7 “OutVolt 0-20”
0-20mA
0 mA = 0 Volts
120% Drive Rated Output Volts
0-20mA
8 “OutPowr 0-20”
0-20mA
0 mA = 0 kW
200% Drive Rated Power
0-20mA
9 “TstData 0-20”
0-20mA
0 mA = 0000
65535 (Hex FFFF)
0-20mA
10 “OutFreq 4-20”
4-20mA
4 mA = 0 Hz
P035 [Maximum Freq]
0-20mA
11 “OutCurr 4-20”
4-20mA
4 mA = 0 Amps
200% Drive Rated Output Current
0-20mA
12 “OutVolt 4-20”
4-20mA
4 mA = 0 Volts
120% Drive Rated Output Volts
0-20mA
13 “OutPowr 4-20” 4-20mA
4 mA = 0 kW
200% Drive Rated Power
0-20mA
14 “TstData 4-20”
4-20mA
4 mA = 0000
65535 (Hex FFFF)
0-20mA
15 “OutTorq 0-10”
0-10V
0V = 0 Amps
200% Drive Rated FLA
0-10V
16 “OutTorq 0-20”
0-20 mA
0 mA = 0 Amps
200% Drive Rated FLA
0-20 mA
17 “OutTorq 4-20”
4-20 mA
4 mA = 0 Amps
200% Drive Rated FLA
0-20 mA
18 “Setpnt 0-10”
0-10V
0V = 0%
100.0% Setpoint Setting
0-10V
19 “Setpnt 0-20”
0-20 mA
0 mA = 0%
100.0% Setpoint Setting
0-20 mA
20 “Setpnt 4-20”
4-20 mA
4 mA = 0%
100.0% Setpoint Setting
0-20 mA