Installation/Wiring

Control Wiring Block Diagram Notes

(1)

Important: I/O Terminal 01 is always a coast to stop input except when

P036

[Start

Source] is set to “3-Wire”, “2-W Lvl Sens” or “Momt FWD/REV” control. In three wire
control, I/O Terminal 01 is controlled by

P037

[Stop Mode]. All other stop sources are

controlled by P037 [Stop Mode].

Important: The drive is shipped with a jumper installed between I/O Terminals 01 and
11. Remove this jumper when using I/O Terminal 01 as a stop or enable input.

(2)

Two wire control shown. For three wire control use a momentary input

on I/O

Terminal 02 to command a start. Use a maintained input

for I/O Terminal 03 to

change direction.

(3)

The function of I/O Terminal 03 is fully programmable. Program with E202 [Digital
Term 3].

(4)

Match the Voltage Range Select DIP Switch setting with the control scheme for proper
Uni-Polar or Bipolar analog input operation.

(5)

When using an opto output with an inductive load such as a relay, install a recovery
diode parallel to the relay as shown, to prevent damage to the output.

(6)

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a
hardware enable, causing a coast to stop without software interpretation.

P036 [Start Source] Stop

I/O Terminal 01 Stop

3-Wire

Per P037

Per P037

(6)

2-Wire

Per P037

Coast

2-W Lvl Sens

Per P037

Per P037

(6)

2-W Hi Speed

Per P037

Coast

RS485 Port

Per P037

Coast

Momt FWD/REV

Per P037

Per P037

(6)