A066, A067, A068 – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 69: Advanced program group, Continued), A066 [analog out high, A067 [accel time 2, A068 [decel time 2, Programming and parameters 3-23

Programming and Parameters
3-23
Advanced Program Group
(continued)
A066 [Analog Out High]
Related Parameter(s):
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
A066 Setting
A065 Setting
A065 Max. Output Value
50%
1 “OutCurr 0-10”
5V for 200% Drive Rated Output Current
90%
8 “OutPowr 0-20”
18mA for 200% Drive Rated Power
A067 [Accel Time 2]
Related Parameter(s):
When active, sets the rate of acceleration for all speed increases except jog.
Values
Default:
20.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Option
Description
28 1
0
0
Acc/Dec 1
0
1
Acc/Dec 2
1
0
Acc/Dec 3
1
1
Acc/Dec 4
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
A068 [Decel Time 2]
Related Parameter(s):
-
When active, sets the rate of deceleration for all speed decreases except jog. Refer to graphic at
[Accel Time 2].
Values
Default:
20.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=