3-30

Programming and Parameters

Advanced Program Group

(continued)

A088 [Maximum Voltage]

Related Parameter(s):

b004

,

A085

,

A086

,

A087

Sets the highest voltage the drive will output.

Values

Default:

Drive Rated Volts

Min/Max:

20/Drive Rated Volts

Display:

1 VAC

A089 [Current Limit 1]

Related Parameter(s):

P033

,

A118

Maximum output current allowed before current limiting occurs.

Values

Default:

Drive Rated Amps

×

1.5

Min/Max:

0.1/Drive Rated Amps

×

1.8

Display:

0.1 Amps

A090 [Motor OL Select]

Related Parameter(s):

P032

,

P033

Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I

2

t

overload function.

Options

0 “No Derate” (Default)

1 “Min Derate”

2 “Max Derate”

Min Derate

0

80

100

60

40

20

No Derate

0

80

100

60

40

20

%

of P033

[Motor OL Curent

]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25