A085, A086, A087 – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 75: Advanced program group, Continued), A085 [start boost, A086 [break voltage, A087 [break frequency

background image

Programming and Parameters

3-29

Advanced Program Group

(continued)

A085 [Start Boost]

Related Parameter(s):

P031

,

P032

,

P034

,

P035

,

A084

,

A086

,

A087

,

A088

,

A125

Sets the boost voltage (% of

P031

[Motor NP Volts]) and redefines the Volts per Hz curve when

A084

[Boost Select] = 0 “Custom V/Hz” and

A125

[Torque Perf Mode] = 0 “V/Hz”.

Drive may add additional voltage unless

A084

[Boost Select] = 5 “0.0 no IR”.

Values

Default:

2.5%

Min/Max:

0.0/25.0%

Display:

0.1%

Frequency

Voltage

A087 [Break Frequency]

P032 [Motor NP Hertz]

P035 [Maximum Freq]

A085 [Start Boost]

P031 [Motor NP Volts]

A088 [Maximum Voltage]

A086 [Break Voltage]

A034 [Minimum Freq]

A086 [Break Voltage]

Related Parameter(s):

P031

,

P032

,

P034

,

P035

,

A084

,

A085

,

A087

,

A088

,

A125

Sets the frequency where break voltage is applied when

A084

[Boost Select] = 0 “Custom V/Hz” and

A125

[Torque Perf Mode] = 0 “V/Hz”

Values

Default:

25.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A087 [Break Frequency]

Related Parameter(s):

P031

,

P032

,

P034

,

P035

,

A084

,

A085

,

A086

,

A088

,

A125

Sets the frequency where break frequency is applied when

A084

[Boost Select] = 0 “Custom V/Hz”

and

A125

[Torque Perf Mode] = 0 “V/Hz”

Values

Default:

15.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz