Velocity StepLogic™, Basic Logic and Timer/Counter Functions

Counter Function

Digital inputs and outputs control the counter function and are
configured with parameters

A051

-

A054

[Digital Inx Sel] set to 19

“Counter In” and 21 “Reset Countr”.

Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level parameters

A056

[Relay Out Level],

A059

[Opto Out1 Level] and

A062

[Opto Out2 Level] are used to set the

desired count value.

Parameters

A055

[Relay Out Sel],

A058

[Opto Out1 Sel] and

A061

[Opto Out2 Sel] are set to 17 “Counter Out” which causes the output to
change state when the level is reached.

Example

A photo eye is used to count packages on a conveyor line.

An accumulator holds the packages until 5 are collected.

A diverter arm redirects the group of 5 packages to a bundling area.

The diverter arm returns to its original position and triggers a limit
switch that resets the counter.

Parameters are set to the following options:

A051

[Digital In1 Sel] set to 19 to select “Counter In”

A052

[Digital In2 Sel] set to 21 to select “Reset Countr”

A055

[Relay Out Sel] set to 17 to select “Counter Out”

A056

[Relay Out Level] set to 5.0 (Counts)