Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 122

background image

4-8

Troubleshooting

Motor and/or drive will not accelerate to commanded speed.

Cause(s)

Indication

Corrective Action

Acceleration time is excessive. None

Reprogram

P039

[Accel Time 1] or

A067

[Accel Time 2].

Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.

None

Compare

b003

[Output Current] with

A089

[Current Limit 1].

Remove excess load or reprogram

P039

[Accel Time 1] or

A067

[Accel

Time 2].
Check for improper

A084

[Boost

Select] setting.

Speed command source or
value is not as expected.

None

Verify

b002

[Commanded Freq].

Check

b012

[Control Source] for the

proper Speed Command.

Programming is preventing the
drive output from exceeding
limiting values.

None

Check

P035

[Maximum Freq] to

insure that speed is not limited by
programming.
Verify programming of

E215

[Speed

Ratio].

Torque performance does not
match motor characteristics.

None

Set motor nameplate full load amps
in parameter

A126

[Motor NP FLA].

Perform

A127

[Autotune] “Static

Tune” or “Rotate Tune” procedure.
Set

A125

[Torque Perf Mode] to

option 0 “V/Hz”.