Installation/Wiring

Hardware Enable Circuitry

I/O Terminal 01 is always a stop input. The status of this input is
interpreted by drive software. If the application requires the drive to be
disabled without software interpretation, a hardware enable
configuration can be utilized. This is done by removing the ENBL
enable jumper and wiring the enable input to I/O Terminal 1 (see below).

1. Remove drive cover as
described on page

1-1

.

2. Locate and remove the Enable
Jumper on the Main Control Board
(see diagram).

3. Wire Enable to I/O Terminal 1
(see

Table 1.I

). The drive will

always coast to a stop regardless of
the settings of

P036

[Start Source]

and

P037

[Stop Mode].

4. If I/O Terminal 01 is used as
hardware enable and 3-wire control
is needed, program one of the
digital inputs for the desired stop
mode.